GCA 6300 USer Accessible Commands: Difference between revisions
(commands) |
(→List of commands: mapping command added) |
||
(5 intermediate revisions by the same user not shown) | |||
Line 1: | Line 1: | ||
This is a list of user accessible commands and useful control characters: |
This is a list of user accessible commands and useful control characters: |
||
=== Commands === |
=== Stepper Commands === |
||
==== List of commands ==== |
|||
COPY – Use this command to copy a file(job) from someone else’ s directory to your own. You will need to know the user log in info and the filename. |
COPY – Use this command to copy a file(job) from someone else’ s directory to your own. You will need to know the user log in info and the filename. |
||
# Log into the account '''you want to copy to''' (for example LOG IN [10,3] ) |
# Log into the account '''you want to copy to''' (for example LOG IN [10,3] ) |
||
Line 33: | Line 35: | ||
LOG OUT – To log out of system. |
LOG OUT – To log out of system. |
||
MAP - command using in mapping (DFAS local alignment mark used for mapping) |
|||
⚫ | |||
⚫ | |||
ORIG- Use this to retune the originate the laser counter/move the stages through their entire motion. |
ORIG- Use this to retune the originate the laser counter/move the stages through their entire motion. |
||
Line 43: | Line 47: | ||
SPEC – Create a job file, must go all the way through to save the job. |
SPEC – Create a job file, must go all the way through to save the job. |
||
=== |
=== Control Characters === |
||
⚫ | |||
==== List of characters ==== |
|||
A – Toggles between left and right alignment die when using non-standard keys. |
A – Toggles between left and right alignment die when using non-standard keys. |
||
Line 56: | Line 60: | ||
O – Vary joystick speed during alignment. |
O – Vary joystick speed during alignment. |
||
F – Each time you press |
F – Each time you press F, it will move the stage about an increasing spiral path away from the initial location. Use this repeatedly to find the alignment marks for samples placed differently on chuck than in initial exposure. |
||
⚫ | |||
CTRL S – stops monitor scrolling function |
CTRL S – stops monitor scrolling function |
Latest revision as of 17:01, 5 May 2021
This is a list of user accessible commands and useful control characters:
Stepper Commands
List of commands
COPY – Use this command to copy a file(job) from someone else’ s directory to your own. You will need to know the user log in info and the filename.
- Log into the account you want to copy to (for example LOG IN [10,3] )
- Account to copy from [10,61]
- Account to copy to [10,3]
- Job to copy: TEST
- LOG IN [10,3]
- COPY
- From? [10,61]TEST.*
- To? [10,3]
COPY–Use this command to copy a file (jobx) to another file (joby) in the same directory. Edit (joby) and make changes if needed.
- COPY JOBx JOBy
DELETE – Removes a file from system
DISP – Display the parameters for a job
EDIT – Use to edit exposure jobs and passes
EX, EXEC – Use this to execute an exposure job
EXPO – Use this to perform a focus and/or exposure calibration
HELP – Use this to find out the syntax and use of any command.
LISTF – Lists a directory of files (LISTF T* will list files starting with T; LISTF *T will list files ending with T).
LOAD – moves the stage to the load position, may be needed if the stage/computer hangs up.
LOG IN [10,xxx] – To log into computer. Each group (or company) has unique LOG IN info.
LOG OUT – To log out of system.
MAP - command using in mapping (DFAS local alignment mark used for mapping)
MODE- You can use this to change the chuck size (from the [10,1] account only) and verify the system focus. Do not change any other parameters or you will throw the system out of calibration!
ORIG- Use this to retune the originate the laser counter/move the stages through their entire motion.
PURGE – Delete files from directory.
RENAME – Rename a file
SPEC – Create a job file, must go all the way through to save the job.
Control Characters
List of characters
A – Toggles between left and right alignment die when using non-standard keys.
D – Sets joystick to move from die to die.
T – Sets joystick to move left alignment die under right objective.
E – Exit out of D or T mode so that joystick is back to normal.
O – Vary joystick speed during alignment.
F – Each time you press F, it will move the stage about an increasing spiral path away from the initial location. Use this repeatedly to find the alignment marks for samples placed differently on chuck than in initial exposure.
CTRL C followed by A and Enter – Abort back to colon prompt
CTRL S – stops monitor scrolling function
CTRL Q – resumes monitor scrolling function