1) Press the lit limit switch to release the stage.
1) Press the lit limit switch to release the stage.


'''Contacts:'''
⚫
Contacts to call if you cannot undo the problem ( '''Do not call after 10 p.m'''. unless there is a real emergency. A deadline for a paper or conference is not a real emergency):


⚫
Who to call if you cannot undo the problem ( '''Do not call after 10 p.m'''. unless there is a real emergency. A deadline for a paper or conference is not a real emergency):
⚫
1) Mike Silva ( Lee Sawyer)


⚫
1) Biljana Stamenic or Lee Sawyer
2) 3C (These guys know all about the stepper, they service it. Ask for Matt, Mike or Adam. 480-892-4433).

2) Mike Silva


3) If neither can be reached, leave a note that stepper is down. E-mail nanofab@ece.ucsb.edu to report a problem.
3) If neither can be reached, leave a note that stepper is down. E-mail nanofab@ece.ucsb.edu to report a problem.

Revision as of 19:45, 7 April 2020

What to do in case of computer (monitor) freeze-up.

Please try these things in this order.

1) Try CTRL C followed by A and Enter. This will abort any command that may have hung up

2) Press RESET on small monitor keyboard.

3) Follow this sequence:

  • a) Pull out upper keyboard.
  • b) Hit “Scroll Lock” button twice followed by the number 2.

This switches the upper monitor from the smart-set computer to the PC control computer. Try a second time if this doesn’t work. You should see a black screen with “Ready” near the top or you will see a menu driven screen. If the monitor switching does not work, go up to the gray interface box on top of the stepper control rack. Press the gray flash button. This is located in the area where the cables all plug in.

  • c) Push in upper keyboard.
  • d) Lift up plastic flap over lower keyboard and press break
  • e) Turn off lower monitor by pulling out the monitor box and using the switch on the top right front corner of the box (DO NOT TURN OFF SYSTEM POWER SWITCH ON MONITOR! This will shut down the whole system)
  • f) Wait 1 minute and turn the monitor back on.
  • g) Let monitor warm up until you see a cursor on the screen.
  • h) Hit the Set Up key on the stepper keyboard (lower keyboard)
  • i) Hit Line/Local key (number 4) so that the on-line LED lights.
  • j) Hit the Set Up key again. You should have a cursor on the screen.
  • k) Pull out upper keyboard and press the Alt button and “O” at the same time.
  • l) Hit Return to start the program.
  • m) Push in upper keyboard.
  • n) At the prompt on the lower monitor, enter the time and date as specified (10:25 19-NOV-02)
  • o) Stepper will finish booting up.
  • p) Pull out upper keyboard and hit “Scroll Lock” button twice followed by the number 1 to transfer monitor back to the smart-set computer. Try a couple times if this does not work and use the flash button (see instruction b) if needed.
  • q) You are ready to Log In.

4) Follow this sequence:

a) Follow system shut down sequence, but DO NOT TURN OFF LAMP OR ENVIRONMENTAL UNIT

b) Wait 5 minutes.

c) Follow system start-up sequence except for instructions on lamp or environmental unit.

What to do if the local alignment or wafer exposure mapping hangs up on the upper monitor.

1) Reset lower Advent computer and wait for reboot.

What to do in case of unplanned power outage.

1) CR Staff will take care of the system in the morning.

What to do for alignment error.

1) Verify that correct alignment key offset is being used

2) Verify that the mask is aligned

3) Verify that the baseline is correct (check values in MODE against the last calibration in the calibration notebook)

4) If you have DFAS alignment marks, perform a MAP job to verify alignment.

What to do for focus resolution problems.

1) Verify system focus using the MODE command

2) Perform a focus optimization job (using command EXPO job name). You will enter exposure time, and focus will vary, You need to enter the increment step. Use one of your jobs that is already written. Use the same type of wafer that you will be using for your real job (substrate type, and thickness). If you need to optimize both (exposure time and focus), you will use the same command EXPO job name, and will enter starting exposure time, and focus, and increment step.

3) Verify that your wafer is not bowed (i.e. under stress from some process)

What to do in case of mask vacuum problem.

1) Check that small pump is running in back of system. Make sure vacuum level is above 20” Hg.

2) Push foot down onto mask with hand so that the vacuum holds the mask.

What to do in case of focus getting stuck and system hanging up.

1) Adjust manual focus knob so that a negative number appears on voltmeter.

2) Note die on computer screen at right of system. Abort using Ctrl-C followed by A. Edit the program and drop out the problem die. If you have exposed some die already, you may want to drop them out too for the second run.

What to do in case of the stage limit going too far (red stage limit light will be lit inside the stepper chamber next to the joystick.

1) Press the lit limit switch to release the stage.

Contacts:

Who to call if you cannot undo the problem ( Do not call after 10 p.m. unless there is a real emergency. A deadline for a paper or conference is not a real emergency):

1) Biljana Stamenic or Lee Sawyer

2) Mike Silva

3) If neither can be reached, leave a note that stepper is down. E-mail nanofab@ece.ucsb.edu to report a problem.